Rosetexwool  Insulation Refractory Co., Ltd.

Concentrated Solar Power

Receiver backing, molten-salt piping and storage tanks. Holds 565°C salt above its 238°C freeze point through the night.

Concentrated solar power is not one insulation problem. Nitrate salt leaves the receiver at about 565 °C, the receiver tube wall is held near 600 °C by corrosion limits rather than by material capability, and the steam side runs at roughly 540 °C. Each of those boundaries needs a different answer, and a fourth — the storage tank base — is a load-bearing structure before it is insulation.

Material temperature rating is only an entry gate, never the selection criterion. We qualify every CSP insulation package against the constraints that actually fail in service: daily thermal cycling, chloride and other leachable ions, molten-salt leak compatibility, and compressive load. This page sets out where each material family belongs, and where it must not be used at all.

System Boundaries

Four Thermal Boundaries, Four Different Answers

A concentrating solar power plant contains several distinct thermal boundaries, and a product that is correct for one is not automatically correct for another. The single most expensive mistake in CSP insulation work is transferring a detail from one boundary to another because the nominal temperature looks the same.

BoundaryTemperature at that boundaryWhat the insulation has to doMaterial family
Irradiated tower receiver tubesTube wall near 600 °C, limited by corrosion in austenitic gradesNothing on the absorber face itself. Flux control and alloy selection carry the dutyNo external insulation on the irradiated surface
Parabolic trough receiverOil or salt side, with heat-loss control inside the glass envelopePreserve the evacuated annulus that provides the thermal resistanceVacuum only. External fibre cannot reproduce it
Receiver rear shell, cavity backing and headersBelow the tube-wall limit but sustainedHold backing-plate temperature and survive wind and cyclingCeramic fibre blankets and modules, calcium silicate board
Hot-salt tank wall and roofAbout 565 °C at the lower shellAbsorb shell growth of roughly 100 mm over a tall tank and stay weathertight at a dense set of nozzlesMineral wool, fibre modules, multilayer systems
Hot-salt tank base565 °C salt down to a controlled concrete interfaceCarry the full salt and tank load while enforcing a temperature gradientRefractory, insulating firebrick, cellular glass
Salt piping, flanges and valvesAbout 565 °CHold salt above its freezing range through the cooldown case, and stay removable at access pointsMineral wool pipe, calcium silicate pipe, removable covers
Steam generator, superheater and main steamAbout 540 °C on the steam sideZone-by-zone selection with personnel protection at access areasCalcium silicate, mineral wool

System-level detail on how these boundaries interact, including the cooldown and freeze-survival calculations behind salt-line thickness, is set out in our CSP insulation system guide.

Material Comparison

MaterialBest fit in a CSP plantService temperatureKey advantageWhere it must not be used
Ceramic fiber blanket / modules / boardReceiver rear shells, cavity backing, high-temperature equipmentup to 1260°C by gradeHigh-temperature capability at low weight, non-combustibleThe irradiated absorber face, and the trough receiver envelope
Calcium silicate (board, pipe)Rigid vessel and equipment cladding, salt pipe, integrated fire plus thermal packagesUp to 1100 °C as a material family; board up to 650 °CStructural, dimensionally stable, A1 non-combustibleThe tank-bottom bearing layer, and anywhere impact damage cannot be inspected
Mineral wool (pipe, board)Salt piping, tank wall and roof, steam linesUp to 650 °CEconomical across the range, A1 non-combustible, good acoustic behaviourThe tank-bottom load path, or any location with uncontrolled leachable ions
Cellular glassHot-salt tank base, cold-salt tank, lower-temperature load-bearing layersWithin the purchased grade declared hot-face limitCompression resistance combined with very low water uptakeAbove its declared hot-face limit; a generic grade name carries no number
Aerogel blanket /nano blanketThickness- or weight-constrained retrofits, removable covers, cramped skid packagesUp to 650 °CLowest thickness per unit of thermal resistanceAnywhere cost per unit of thermal resistance dominates over space
Glass woolPlant buildings and HVAC services only, not the solar hot boundary–120 to 400 °CLow cost and low densityAny salt boundary, tank or high-temperature equipment

Application Scenarios

Concentrated Solar Power Application Scenarios

  • Tower receiver rear shell and cavity — Ceramic fibre modules and blankets insulate the non-irradiated backing behind the absorber tubes. The tubes themselves stay exposed to the heliostat field, because their protection comes from alloy selection, flow distribution and flux control.
  • Parabolic trough loop — the receiver is an optical vacuum component whose thermal resistance is the evacuated annulus between the selective absorber and the glass envelope. It is not a pipe that needs more lagging, and external fibre would block the aperture the receiver depends on. The insulated boundary is the field piping, headers and heat exchangers.
  • Molten-salt storage tank wall and roof — Mineral wool or fibre modules with slip planes and expansion captures handle shell growth and nozzle density, and keep standby heat loss under control.
  • Molten-salt storage tank base — refractory, insulating firebrick and cellular glass work as separate structural and thermal layers, carrying the salt load while stepping temperature down toward the concrete.
  • High-temperature molten-salt piping, flanges and valves — Mineral wool pipe and calcium silicate pipe on fixed runs, with removable covers at joints that are opened for maintenance.
  • Steam generator and steam cycle — zoned calcium silicate and mineral wool, with personnel protection where operators need access.

Storage Tank Base

The Storage Tank Base Is a Load-Bearing Layer Stack

The base of a hot salt tank has to turn roughly 565 °C salt conditions into temperatures acceptable to structural concrete and the ground, while carrying the full weight of salt, tank and foundation. This is the one place in a CSP plant where the insulation performs a structural function, and where a thermal-only approach is simply unsafe.

Layer or function, from salt downwardWhat it doesWhy the layer cannot be omitted or merged
Tank bottom plate with internal liner or protectionContains the salt and distributes loadLiner selection depends on the vessel concept, not on a standard template
Refractory hot-face or load-spreading layerTakes high temperature and spreads compressive loadRefractory on its own is not a liquid-tight barrier
Insulating firebrickHigh-temperature thermal resistance with bearing capacityJoint quality governs real performance, not the data sheet alone
Cellular glassLower-temperature insulation, compression resistance and low water uptakeThe purchased grade hot-face limit governs, not the material family name
Reinforced-concrete slab or pedestalCarries structural load and must stay within its moisture and temperature basisA published interface limit is a project criterion, not a universal allowable
Ventilation or passive cooling where requiredLimits soil and concrete temperatureNot always preferable to thermal resistance; it is a design choice to be justified

Mineral wool is generally unsuitable here, and the objection is mechanical rather than thermal: resilient batts do not provide a predictable, maintenance-free bearing path for concentrated vertical loads, differential settlement and long-duration compression. A composite arrangement is not impossible if an independent structural system carries the load, but then settlement, moisture and salt-leak consequences have to be demonstrated rather than assumed.

Salt and Chloride

Salt Compatibility and Chloride Control

Two different chemistries have to be handled separately, and they fail in different ways. Leachable chloride, fluoride, silicate and sodium ions migrate with moisture, concentrate at the metal surface as water evaporates, and attack austenitic stainless steel from the outside. Molten nitrate salt is a separate problem: it is a strong oxidiser, it wets metal, it freezes near 220 °C, and it supports the combustion of organic material.

Material or detailPosition in a CSP plantReason
Mineral wool and fibre blanketsPermitted on external salt boundaries with product qualificationNot a leak barrier; must be openable and replaceable in the affected zone
Cellular glass and closed-cell systemsPermitted where the hot-face limit allowsLow water uptake, but joints and the grade limit still govern
Aluminium jacketing in a salt-leak zoneAvoidNitrate salt attacks aluminium, and a leak reaching the jacket destroys the weather barrier
Copper alloys and galvanised components in the leak pathAvoidChemical and galvanic incompatibility with nitrate salt
Organic binders and combustible facings at the hot faceAvoidNitrate salt supports combustion of organic material
Insulation presented as secondary containmentNever acceptableThe leak path must be designed independently of the insulation

Where stainless steel is involved, the purchase order should ask for a preproduction external-stress-corrosion assessment for the supplied product family together with water-leachable ion results on an agreed lot basis. Asking for low chloride without naming an extraction method and an acceptance basis is not a requirement, it is a wish.

Material Selection Guide

How to Select CSP Insulation

  1. Define the boundary before the product. Irradiated absorber surface, non-irradiated receiver backing, tank shell, tank base, salt pipe, valve and steam line are six different problems. Write the boundary down, then select.
  2. Fix the governing figure, not the headline figure. About 565 °C is salt temperature, near 600 °C is a tube-wall limit in specific alloys, and about 540 °C is steam. They are not interchangeable in a thickness calculation.
  3. Size salt lines on the cooldown case. Steady-state heat loss rarely governs. What governs is how long a stagnant line may sit before salt reaches its freezing range, which also decides whether trace heating is a backup or a primary function.
  4. Treat the tank base as structure. Refractory, firebrick, cellular glass and concrete each do a different job. A compression figure quoted at ambient temperature does not qualify a bearing layer.
  5. Put chloride and salt exposure in the specification. Require leachable-ion results for austenitic steel contact and state the salt-leak response, removal and disposal expectations up front.
  6. Detail for daily cycling. Between roughly 290 °C at night and 565 °C by day, movement must be made repeatable rather than restrained: slip planes in the jacketing, expansion captures at terminations, sealing that does not bond moving parts together, and drainage at every low point.
  7. Keep it inspectable and replaceable. Removable covers at valves and flanges, openable details at high-risk tank locations, and a defined replacement route for any zone that could see a salt leak.

Material-level detail sits on our ceramic fibre, calcium silicate, mineral wool, aerogel and glass wool pages. Where the comparison moves from engineering to whole-life cost, our insulation material cost comparison sets out the basis.

Standards & Compliance

CSP Insulation Standards

Most building-insulation products are outside their range at CSP temperatures, so the relevant documents are the high-temperature product standards, the fire-classification standards and the calculation rules. There is one important qualification at the end of this section about a dedicated CSP insulation standard.

DocumentWhat it governsNote for CSP work
EN 14303Factory-made mineral wool for building equipment and industrial installationsIts scope extends to about 800 °C, which is a scope statement, not a product temperature rating. Declared values come from the test methods the standard cites
EN 14306Factory-made calcium silicate productsCovers the calcium silicate family used on vessels, pipe and fire-thermal packages
EN 13501-1, Class A1Reaction-to-fire classificationSupports the non-combustible claim for mineral wool and calcium silicate systems
ASTM C547Mineral fibre pipe insulation, Type I to Type VType designation is the whole specification. Type I and Type V are not interchangeable
ASTM C533Calcium silicate block and pipe insulationThe North American counterpart to the EN calcium silicate route
ASTM C612 / ASTM C553 / ASTM C592Mineral fibre block and board, and blanket for industrial applicationsProduct-family level; type and grade still carry the limits
ASTM C552Cellular glassIts inherent scope stops at about 427 °C, with application limits agreed between manufacturer and purchaser. The grade, not the family name, carries the hot-face number
ASTM C795 / ASTM C692 / ASTM C871Insulation in contact with austenitic stainless steel, external stress-corrosion assessment, and water-leachable ion analysisThese three are how chloride control becomes testable rather than aspirational
ISO 12241Calculation rules for heat transfer in industrial installationsPredominantly steady-state. It sizes a system; it does not qualify one for start-up, cloud passages or tank filling
IEC 62862 seriesSolar thermal electric plants: terminology, resource, performance testing, heat-transfer fluids, storage characterisation, trough and tower plant design, receivers, heliostat control, linear FresnelThe receiver part covers receiver-level heat-loss tests, not pipe or tank insulation. See the qualification below

On a dedicated CSP insulation standard. A project for thermal insulation of solar thermal electric plants has been identifiable in the technical committee project list. As of the published-parts list reviewed for this page, no dedicated insulation part had been verified as published. So the accurate statement is that a dedicated project exists while no published insulation part had been confirmed. Until such a document is contractually applicable, a CSP specification has to be assembled from product standards, calculation rules and owner acceptance criteria. Saying there is no CSP insulation standard at all overstates the case and is easy to disprove.

The European and American pipe insulation standards declare quite different things, and the comparison is worth reading before a dual-standard tender, in our EN 14303 vs ASTM C547 guide.

Cycling and Inspection

Daily Cycling, Inspection and Procurement

CSP cycling loads the insulation assembly, not only the pressure boundary. As the pipe or tank cycles between roughly 290 °C and 565 °C, it grows relative to the insulation and jacket and then contracts again. The failure modes below repeat across projects, and none of them appears in a steady-state heat-loss calculation.

Failure modeWhere it appears firstCountermeasure
Open butt joints and staggered seamsLong straight runs, changes of directionSpecify cyclic movement allowance at every joint, not only at anchors
Blanket pumping through loose restraintsVertical runs and tank shellsPositive restraint and correct band spacing; no friction-only fixings
Cracking of rigid boardTank shells, vessel heads, valve boxesSegmented or compliant details where differential growth is high
Loosened bands, clips and anchor pinsHigh-vibration zones and machine-adjacent pipingAnchors selected for cyclic duty; inspection as a scheduled item
Deformed removable coversValve and flange boxesTest the reuse claim over the real removal count before acceptance
Fatigue of jacket laps and end closuresLong runs, tank shells, roof perimeterSlip planes and expansion captures in the jacketing
Breached sealant at penetrationsNozzles, platform legs, ladder bracketsSeal without bonding moving parts together; drain every low point

Water entering through any of those openings is driven off at the next heat-up, which concentrates dissolved ions at the metal surface. That wet-dry cycle is why the weather barrier and the leachable-ion requirement belong in the same specification. The detailing side is covered in our cladding and jacketing guide.

For procurement, the four clauses that carry the most weight are a stated design boundary in writing, a stainless-steel compatibility requirement with test evidence, mechanical duty data at the project temperature and load duration, and an explicit statement that insulation is not secondary containment. How to verify the documents behind those clauses is set out in our industrial insulation supplier selection guide.

Molten Salt & Freeze Protection

Molten Salt Lines: Freeze Protection and Heat Tracing

Binary nitrate salt freezes at about 238 °C and decomposes above roughly 600 °C, which leaves a working band of some 330 degrees and an absolute requirement that the line never drops out of it. A frozen salt line is not a nuisance — it is a plug that can cost weeks of generation.

Insulation on salt piping therefore serves two masters: it holds the temperature during normal circulation, and it reduces the heat that tracing has to supply when the line is stagnant at night or during a freeze-protection event. Thickness is chosen from the cooldown time the operating strategy allows, not only from steady-state heat loss.

Valves, flanges and instrument tappings are the freeze points. Each one needs tracing, insulation and a removable cover that can be refitted in a hurry, and the design should assume a maintenance crew working at night with the plant trying to restart.

Parabolic Trough

Parabolic Trough Collectors and Receiver Tubes

Parabolic trough plants use a different working fluid and a different insulation problem. A heat-transfer oil loop runs to roughly 390 to 400 °C, the receiver is a steel tube inside an evacuated glass envelope, and the insulation duty sits at the joints rather than along the tube.

Between adjacent collector elements, the receiver uses flexible bellows and a shield to cover the expansion gap. That shield and the insulation around it are what stop a small, repeated convection loss from becoming a measurable share of the field's output, multiplied by the thousands of joints in a commercial plant.

At the field headers and the hot/cold manifold, conventional high-temperature insulation takes over: calcium silicate or rock wool sections on the header piping, with the freeze-protection logic running through the same tracing design as any process plant.

Steam Cycle & BOP

Steam Generation, Turbine and Balance of Plant

Whatever the collector technology, the back end of a CSP plant is a steam plant: a solar steam generator, a turbine at roughly 540 °C inlet, feedwater trains, and the piping that connects them. Insulation here follows conventional power-station practice rather than solar-specific rules.

Main steam and hot reheat lines use calcium silicate or high-temperature rock wool sections sized to keep the outer surface within personnel limits; the turbine and its valve chests get removable covers so the machine can be opened without destroying the lining. Feedwater and condensate lines are cooler and cheaper to insulate, but they are where the largest surface area sits.

In a plant that starts and stops daily, the thermal mass of the lining matters as much as its conductivity. Lightweight build-ups with low heat capacity reach operating temperature faster and lose less energy on every cycle, which is one reason ceramic fiber appears in the high-temperature sections of a cycling solar plant.

Storage Tanks

Storage Tanks: Shell, Roof and Nozzle Insulation

A two-tank molten salt system stores the plant's entire thermal output in two large vessels at 290 °C and 565 °C. Their shells are the largest insulated surface on the site, and their losses are continuous — a tank does not stop losing heat when the sun goes down.

The shell is typically lined with mineral wool board or blanket in two layers with staggered joints, finished with a metal jacket detailed to shed water. The roof is the neglected half: it sees the highest salt temperature, the most thermal movement and the worst access, and roof insulation that is compressed or missing shows up as an unusable top salt layer.

Nozzles, manways and instrument connections interrupt the lining on both shell and roof. Each one needs an insulated, sealed and removable closure, and the design must accept the tank's own thermal growth — several tens of millimetres on a large diameter — without tearing the jacket.

Commissioning & Testing

Commissioning, Heat-Up and Performance Testing

A CSP plant is commissioned by heating it slowly. The salt system is brought up through its freeze range under controlled conditions, the receivers are dried out before the first focus, and the insulation is expected to survive the whole sequence without cracking, spalling or losing contact with the surface it protects.

Dry-out is the step most often rushed. Any cementitious or castable component in the lining carries free water that has to leave below 150 °C, and a heat-up curve that runs ahead of it will spall the material from the inside. The same applies to moisture trapped behind a vapour barrier on cold-side equipment.

Acceptance is then measured, not assumed. A heat-loss or cooldown test on a tank or a pipe section compares the installed performance with the design value, and thermal imaging identifies the joints where the two diverge. On a plant with a 25 to 30 year design life, that first survey becomes the baseline for every later inspection.

Related Applications

Concentrated solar power relies on high-temperature thermal storage, a steam cycle and a large heat-transfer piping network. Related high-heat applications:

Why Rosetexwool

Key Benefits

Why Concentrated Solar Power operations choose Rosetexwool insulation solutions.

High-Temp Stability

Ceramic fiber and calcium silicate withstand molten-salt and receiver operating temperatures in CSP plants.

Thermal Efficiency

Receiver and pipe insulation cuts heat loss, raising plant output and capacity factor.

Corrosion Resistance

Chemically stable materials resist molten-salt and tower-environment corrosion.

Long Service Life

Durable linings reduce downtime in high-temperature CSP loops.

Support

Frequently asked questions

What insulates CSP receivers and towers? +

Ceramic fibre blankets and modules insulate the non-irradiated parts of a receiver: the rear shell, cavity backing, headers and adjacent structure. The absorber tubes that face the heliostat field are not insulated at all, because their protection comes from alloy selection, flow distribution, coating and flux control. On the parabolic trough side there is no external insulation on the receiver either, since its thermal resistance is the evacuated annulus inside the glass envelope.

How do you insulate molten-salt storage? +

There are two completely different problems inside one tank. The wall and roof are an ordinary external boundary carrying an unusual duty: the shell grows roughly 100 mm over the height of a tall tank at salt temperature and is interrupted by a dense set of nozzles, so mineral wool or fibre modules with slip planes and expansion captures work better than rigid systems anchored to both shell and platform. The base is a load-bearing layer stack of refractory, insulating firebrick, cellular glass and concrete that carries the salt load while stepping temperature down to a controlled concrete interface.

Why can mineral wool not be used under a molten salt tank? +

The objection is mechanical, not thermal. A tank base needs a predictable, durable bearing path for concentrated vertical loads, differential settlement and long-duration compression, and resilient batts cannot provide that. Cellular glass combines compression resistance, low water uptake and thermal resistance in one layer, which is why it appears in that position. The accurate statement is that mineral wool is generally unsuitable as a tank-bottom bearing layer, not that it is prohibited everywhere on a CSP site.

Do you offer integrated fire-thermal solutions? +

Yes. We supply combined fire and thermal insulation packages in calcium silicate and mineral wool for CSP equipment, tanks and piping, classified A1 non-combustible under EN 13501-1.

What temperature can ceramic fiber withstand in CSP? +

Ceramic fibre grades are classified from 1100 to 1430 °C depending on chemistry, and continuous-use limits sit below the classification temperature, so the governing figure always comes from the grade data sheet for the specific application. In CSP the point is that ceramic fibre is used on non-irradiated receiver structure and high-temperature equipment; molten-salt storage and distribution at about 565 °C is normally served by mineral wool and calcium silicate.

Is your solar-plant insulation non-combustible and corrosion resistant? +

Mineral wool and calcium silicate systems are A1 non-combustible under EN 13501-1. Corrosion resistance is a separate and testable property rather than a claim: for any insulation in contact with or draining toward austenitic stainless steel we provide preproduction stress-corrosion qualification for the supplied product family plus water-leachable chloride, fluoride, silicate and sodium results on an agreed lot basis.

Why is the trough receiver not insulated like a normal pipe? +

Because its thermal resistance is created inside the component, in the evacuated annulus between the selective absorber and the glass envelope. External fibre adds resistance only at the outer glass surface, which is the least significant loss path, and it blocks the optical aperture. A receiver losing performance needs residual-gas diagnosis and an approved repair or replacement route, not more lagging.

Is there a dedicated CSP insulation standard? +

A project for thermal insulation of solar thermal electric plants has been identifiable in the technical committee project list, but as of the published-parts list reviewed for this page no dedicated insulation part had been verified as published. The receiver part of the solar thermal electric plant series covers receiver-level heat-loss tests rather than pipe and tank insulation. Until such a document is contractually applicable, a CSP specification is assembled from product standards such as EN 14303, EN 14306, ASTM C547, ASTM C533 and ASTM C552, plus calculation rules and owner acceptance criteria.

How do you control chloride attack in a CSP plant? +

By making it testable. Water-leachable chloride, fluoride, silicate and sodium content is declared by the specified extraction and analytical method, external stress-corrosion assessment is requested for the product family in contact with austenitic stainless steel, and lot traceability links the delivered material to the tested type. The weather barrier matters just as much, because water entering a jacket lap is driven off at the next heat-up and concentrates ions exactly at the metal surface.

Last updated: November 6, 2026

Ready to start? Tell us your specs — we'll quote within 24 hours.

Get pricing

Request a quote for Concentrated Solar Power solutions

Tell us about your concentrated solar power project requirements — our team responds within one business day.

Free sample + 24-hour engineering quote

  • Free cut-to-size samples for lab testing or plant trial, shipped by courier.
  • Material recommendation, drawings and an FOB or CIF price within one working day.

Spec-match guarantee

  • Every batch tested against the MTC and TDS that ship with your order.
  • Off-spec material: we re-ship or refund in full, freight both ways on us.
or email us directly
Request a Quote WhatsApp

Get in touch

Free consultation & tailored quotation

Request a Quote WhatsApp